Capacitor or reactor banks connected to AC buses or branches. For groups or banks connected to the same bus, minimum and maximum voltage, controlled bus and voltage control strategies will always be the same. In that sense, capacitors/reactors connected to a branch are considered as connected to the bus of the end which they are connected.
Column | Description |
---|
From bus | Either the bus number which shunt capacitor/reactor banks are connected or bus number from one of the circuit ends where line capacitor/reactor banks are connected. |
Operation | Groups or banks addition, removal or modification |
To bus | Bus number from the other end where line capacitor/reacor banks are connected; Not used for shunt capacitor/reactor banks |
Circuit | AC circuit identification number |
Control mode | Automatic switching control; C for continuous, D for discrete and F for fixed |
Minimum voltage | Lower bound for voltage range that determinates automatic switching control |
Maximum voltage | Upper bound for voltage range that determinates automatic switching control |
Controlled bus | Bus number which voltage will be controlled by automatic switching control or reactors connected to the bus defined in Bus field; Controlled voltage value depends on the fields Control and Control Type |
Initial reactive injection | Initial reactive injection due to capacitor/reactor banks connected in the bus (Mvar); This field aims to represent initial reactive power injection value for power flow solving; If control mode is fixed, this value represents what is effectively injected in the bus |
Control type | C if control is made by the center of the voltage range, L if it is made by the violated bounds |
Erase DBAR data? | If filled with 'S', value in Capacitor/Reactor field (DBAR section) will be erased |
Extremity | Bus number from the circuit end where shunt capacitor/reactor banks are connected to |
Column | Description |
---|
Group or bank | Identification number; Each group or bank can have one or more switching stages |
Operation | Capacitor/reactor banks or group data addition, removal or modification |
Status | L if the group or bank is on, D if it is off |
Unities | Total number of unities or stages that constitute the group or bank. This field is used as memory of the total number and the maximum allowed for each bus is 6 |
Operating unities | Total number of unities or stages that constitute the group or bank that are effectively in operation |
Capacitor reactor | Total reactive power injected by one unity(Mvar); This value refers to the injected reactive power at nominal voltage (1.0 p.u.) and should be positive for capacitors and negative for reactors |