DBSH

Description

Capacitor or reactor banks connected to AC buses or branches. For groups or banks connected to the same bus, minimum and maximum voltage, controlled bus and voltage control strategies will always be the same. In that sense, capacitors/reactors connected to a branch are considered as connected to the bus of the end which they are connected.

Usage

ColumnDescription
From busEither the bus number which shunt capacitor/reactor banks are connected or bus number from one of the circuit ends where line capacitor/reactor banks are connected.
OperationGroups or banks addition, removal or modification
To busBus number from the other end where line capacitor/reacor banks are connected; Not used for shunt capacitor/reactor banks
CircuitAC circuit identification number
Control modeAutomatic switching control; C for continuous, D for discrete and F for fixed
Minimum voltageLower bound for voltage range that determinates automatic switching control
Maximum voltageUpper bound for voltage range that determinates automatic switching control
Controlled busBus number which voltage will be controlled by automatic switching control or reactors connected to the bus defined in Bus field; Controlled voltage value depends on the fields Control and Control Type
Initial reactive injectionInitial reactive injection due to capacitor/reactor banks connected in the bus (Mvar); This field aims to represent initial reactive power injection value for power flow solving; If control mode is fixed, this value represents what is effectively injected in the bus
Control typeC if control is made by the center of the voltage range, L if it is made by the violated bounds
Erase DBAR data?If filled with 'S', value in Capacitor/Reactor field (DBAR section) will be erased
ExtremityBus number from the circuit end where shunt capacitor/reactor banks are connected to

Capacitor/Reactor banks

ColumnDescription
Group or bankIdentification number; Each group or bank can have one or more switching stages
OperationCapacitor/reactor banks or group data addition, removal or modification
StatusL if the group or bank is on, D if it is off
UnitiesTotal number of unities or stages that constitute the group or bank. This field is used as memory of the total number and the maximum allowed for each bus is 6
Operating unitiesTotal number of unities or stages that constitute the group or bank that are effectively in operation
Capacitor reactorTotal reactive power injected by one unity(Mvar); This value refers to the injected reactive power at nominal voltage (1.0 p.u.) and should be positive for capacitors and negative for reactors

Example

Alt text