DCSC

Description

Controllable series compensator data

Usage

ColumnDescription
From busBus number, as defined on DBAR, from on of the compensator ends
OperationCompensator data addition, removal or modification
To busBus number, as defined on DBAR, from the other compensator end
CircuitAC circuit identification number
StatusCircuit status
OwnerF if the circuit belongs to the area from the bus in From bus, T if it belongs to To bus area
BypassL if bypass is on, D if it is off
Minimum valueCompensator reactance minimum value (%)
Maximum valueCompensator reactance maximum value (%)
Initial valueCompensator reactance initial value (%)
Control modeP for constant power, where active power flow specified value is kept while compensator reactance values are kept in bounds; I for constant current, where the current module specified value is kept while compensator reactance values are kept in bounds; X for constant reactance, where the compensator is not used and reactance is fixed at the specified value
Specified valueIf control mode is constant power, active power flow in the compensator (MW); If control mode is constant current, compensator current module (p.u.); If control mode is constant reactance, compensator reactance (%)
Measuring extremityBus number from the compensator end where power or current is measured
Number of stagesNumber of stages for discrete compensators (Thyristor Switched Series Capacitor); Default value for continuous compensators (Thyristor Controlled Series Capacitor)
Aggregator 1-6Additional information